Actuator connection
2 x (2-wire, 3-wire)
Contact resistance (max.)
0.03 Ω
Contact resistance (typ.)
2.1 Ω
Current carrying capacity (power jumper contacts)
10 A
Current consumption (5 V system supply)
10 mA
Drop-out time (max.)
3 ms
Drop-out time (typ.)
0.1 ms
Indicators
LED (A, C) green: Status DO 1, DO 2
Isolation
1500 V (system/field)
Load type
Resistive, inductive
Making capacity (current/time)
0.5 A (20 s)
Making capacity (current/time) (2)
1.5 A (0.1 s)
Number of digital outputs
2
Number of incoming power jumper contacts
3
Number of outgoing power jumper contacts
3
Output characteristic
non-floating
Output circuit design
Solid-state load relays
Output current per channel
0.3 A
Output data width (internal) max.
2 Bit
Protection against incorrect wiring
Overvoltage protection (275 V) via varistor
Pull-in time (max.)
10 ms
Pull-in time (typ.)
4 ms
Signal type
Voltage
Signal type (voltage)
0 … 250 VAC/DC
Supply voltage (field)
250 VAC/DC; via power jumper contacts (power supply via blade contact; transmission (supply voltage field side only) via spring contact)
Supply voltage (system)
5 VDC; via data contacts
Switching frequency (max.)
5 Hz; 24 V; 0.3 A; DF = 50 %
Switching frequency (max.) (2)
0.5 Hz; 230 V; 0.3 A; DF = 50 %
Total number of channels (module)
2